9 GENERAL INFORMATION Your Mendota Gas Fireplace has a state-of-the-art co-axial direct vent, sealed combustion system. This advanced, highly effic
10 VENT OPTIONS DISCUSSION This Mendota Fireplace can be vented using AMERIVENT, DURAVENT, SELKIRK METALBESTOS, SECURITY CHIMNEY and ICC brands of c
11 GAS SUPPLY REQUIREMENTS Correct gas pressure and proper gas supply line sizing is imperative to the successful performance of your Mendota gas fi
12 GAS PRESSURE REQUIREMENTS A MAJOR CAUSE OF OPERATING PROBLEMS WITH GAS APPLIANCES CAN BE IMPROPER GAS PRESSURE! Problems such as changes in flame
13 EXTERIOR VENT LOCATIONS AND RESTRICTIONS Figure 2: Exterior Vent Locations ALL MEASUREMENTS GIVEN ARE FROM THE CENTER LINE OF VENT CAP ∨ - Vent
14 GENERAL FLUE VENTING INSTRUCTIONS The Mendota Fireplace must be vented using Amerivent, Duravent, Selkirk Metalbestos, Security Chimney or ICC Br
15 GENERAL INSTALLATION INSTRUCTIONS CAUTION: Each installation must conform to all local, state and national codes. Refer to the national fuel gas
16 outage, turn off the burners for 1 hour and allow the fireplace to cool down. Consecutive 1-1/2 hour burn and 1 hour cool down cycles are allowed
17 TOP FLUE VENTING COMPONENTS ITEM DESCRIPTION 1 12" VENT STACK 1 24" VENT STACK 1 36" VENT STACK 1 48" VENT STACK 2 90ºGALVA
18 FLUE VENTING ALLOWANCE CHART NOTE: FOR LP GAS & HIGH ALTITUDE, SEE PG. 19 NOTE: FOR LPG AND HIGH ALTITUDEAPPLICATIONS, SEE PAGE 19. NOTE: 1
In the Commonwealth of Massachusetts: • Installation must be performed by a licensed plumber or gas fitter; • A CO
19 L.P. GAS MINIMUM HEIGHT HORIZONTAL TERMINATION For L.P. gas and high altitude installations (above 4,000 ft.), 45° elbows must be used in plac
20 MINIMUM RISE THROUGH-THE-WALL VENTING: The minimum vertical rise for vent installation through the wall is 16 1/4" from the top of the firep
21 VENTING COMPONENTS LIST NOTE: ALL PART NUMBERS LISTED ABOVE APPLY TO SIMPSON DURAVENT COMPONENTS ONLY. MENDOTA # DESCRIPTION45-01-00186 7&quo
22 ELEVATED VERTICAL RISE THROUGH-THE-WALL VENTING The required MINIMUM vertical rise is 48 in. when used with a maximum horizontal run of 12 ft. F
23 VERTICAL THROUGH-THE-ROOF VENTING The maximum vertical run of vent pipe is 55 ft. from the top of the fireplace. The fireplace will support a ru
24 2.) PULL3.) ROTATE4.) RELEASE1.) INSERTDOOR REMOVAL AND REPLACEMENT CAUTION: Do not operate the appliance with glass removed, cracked or broken.
25 GLASS FRAME ASSEMBLY REPAIR AND REPLACEMENT TO REPLACE DAMAGED GLASS 1. Using a 1/8” drill bit, drill through 3 rivets on each side of glass f
26 DXV-35 DT3 DEEP TIMBER LOG SET INSTALLATION INSTRUCTIONS FOLLOW EACH STEP DEPICTED IN THE DIAGRAMS, BELOW, TO INSTALL THE LOG SET. CAUTION: LOGS
LOG# 1 PLACE LOG #1 (REAR LOG) ON REAR SHELF BEHIND REAR BURNER. SLIDE LOG TO RIGHT UNTIL LOG TOUCHES RIGHT SIDE BRICK PANEL. PUSH LOG BACK SO IT TOUC
LOG #2 LOG #2 LOG #2 (MID EMBER BED) SITS BETWEEN REAR AND FRONT BURNER, FLAT DOWN ON THE SURFACE OF THE BURNER AIRBOX. ADJUST POSITION OF FRONT AND R
2 DXV35 DT3 FEATURES - QUICK REFERENCE INFORMATION EXTERNAL DIMENSIONS: 35-7/8” Wide X 31-1/2” High X 15-1/2” Deep MINIMUM FRAMING DIMENSIONS: 37-1
LOG #2 LOG# 1 LOG# 3 PLACE LOG #3 (LEFT LOG) ON TOP OF THE RECTANGLE AIR SHUTTER BOX ON THE LEFT SIDE. LOG #3 HAS A RECTANGULAR NOTCH ON ITS BOTTOM SI
LOG #4 LOG #4 (RIGHT LOG) HAS A HOLE FOR THE PIN ON LOG #2. INSERT PIN IN LOG #2 INTO HOLE IN LOG #4. SET RIGHT END OF LOG #4 ON TOP OF THE FIRST GRAT
LOG #2 LOG# 1 LOG# 3 LOG# 4 LOG# 5 LOG #5 (LEFT TOP LOG) SITS ON THE LEFT SHOULDER OF LOG #1 AND ITS TWO BRANCHES SIT ON TOP OF LOG #2 AND LOG #3. LOG
LOG #6 (RIGHT TOP LOG) SITS ON TOP OF LOG #1 USING THE PIN THAT IS ON THE RIGHT SIDE OF LOG #1. LOG #6 HAS A HOLE IN ITS BACK-SIDE TO MATE WITH THIS P
LOG# 4 LOG# 7 LOG# 7 LOG #7 REST ON TOP OF THE FRONT BURNER’S REAR VISIBLE EDGE AND ON TOP OF LOG #4. THIS LOG IS DESIGNED TO HIDE THE PILOT LIGHT. P
LOG# 2 LOG# 8 LOG# 8 PLACE LOG #8 ( LEFT FRONT TWIG) IN THE POSTION SHOWN HERE. LOG #8 SITS ON TOP OF LOG #2 AND RESTS AGAINST THE GRATE BAR (2ND FROM
LOG# 9 LOG #9 (RIGHT FRONT CHUNK) IS TO BE PLACED AT A SEVERE ANGLE AGAINST THE HORIZONTAL GRATE BAR AND FLOATING OVER THE FRONT BURNER PORTS. THE POS
COMPLETED LOG SET ASSEMBLY
37 The following Check Off Lists must be completed prior to final operation of the Fireplace, or manufac-turer's warranty and liabilities will
38 BEFORE YOU BEGIN Read this entire manual before you use your new fireplace (especially the section “Safety Precautions” on page 2). Failure to
3 TABLE OF CONTENTS FOR YOUR SAFETY READ BEFORE LIGHTING ...
39 REMOTE TRANSMITTER OPERATING INSTRUCTIONS TO TURN ON THE APPLIANCE: 1. Press the ON/OFF button. The transmitter display will show all active
40 TEMPERATURE INDICATOR (oF or oC) 1. Press the ON/OFF Key and Turn Off the Fireplace. 2. Simultaneously, Press both the MODE Key and the Thermosta
41 “FIRST TIME” PILOT LIGHTING INSTRUCTIONS IMPORTANT: Be sure all items on "INSTALLATION CHECK OFF LIST" in the Installation Manual have
42 ATTENTION! • The transmitter and receiver are RADIO FREQUENCY DEVICES. • Turn off the main gas supply of the appliance during installation or
43 Backup Batteries Backup Batteries are to be installed in the Battery Pack located on the right side of the Courtesy Panel beneath the glass frame
44 BLOWER OPERATION AND WIRING WARNING: The Electrical Junction box within this appliance must be connected to a grounded LIVE power circuit. No swi
45 TROUBLE SHOOTING MENDOTA GAS DXV FIREPLACE SYMPTOM PROBABLE CAUSES CORRECTIVE ACTION 1. Thin black coating (soot) forms on viewing glass. A.
46 CUSTOMER INFORMATION AND TROUBLE-SHOOTING MAXIMUM ALLOWABLE SURFACE TEMPERATURE Mendota Fireplaces comply with UL Standards for maximum surface t
47 MAINTENANCE 1. ANNUAL MAINTENANCE OF MENDOTA UNITS IS REQUIRED. The following procedures must be performed each year by a Mendota approved serv
48 WIRING SCHEMATICS Note: The DXV35-DT3-LX ignition system utilizes Transformed DC power for normal ignition functions. In the event of a power out
4 SPECIFICATIONS MODEL DXV-35 DT3 INPUT RATES (Btu/Hr) High Fire - Adjustable to - Low Fire NAT. GAS 33,000 10,000 LP GAS
49 NATURAL TO LP GAS CONVERSION INSTRUCTIONS Kit # HA-30-00507 Mendota Model DXV35 DT3 This conversion kit shall be installed by a qualified servic
50 5. Using a ½” deep well socket wrench, remove Front and Rear Orifices. 6. Thread a new 3/64” drilled orifice to both Front and Rear Orifice mo
51 10. Before reinstalling burners, loosen the screw that secures the rotary air shutter on the Front Burner. Rotate the air shutter open to ¼” min
52 INSTALLING THE LP PRESSURE REGULATOR WARNING: READ AND UNDERSTAND ALL INSTRUCTIONS PACKAGED WITH LP PRESSURE REGULATOR BODY BEFORE YOU ATTEMPT TH
53 INLET TAP OUTLET TAP LP GAS PRESSURE REQUIREMENTS Inlet and manifold gas pressure checking taps are located on gas valve. These ports are only ac
54 WARNING DO NOT PROCEED WITH OPERATION OF THIS FIREPLACE UNLESS BURNER "CYCLES" ON/OFF WITHOUT DELAYS! CHECKING FOR NORMAL BURNER (S) I
55 REPLACEMENT PARTS MENDOTA GAS DXV-35 DT3 FIREPLACE PART NO DESCRIPTION PART NO DESCRIPTION 65-02-00103 TADPOLE GLASS GASKET (106”) 05-04
56 MENDOTA DESIGNER FRONTS INSTALLATION INFORMATION The following Designer Fronts are available for the DXV-35 Fireplace: 1. Andover, Bentley Arc
57 HEARTH PAD SURFACE MUST BE FLUSH WITH FIREPLACE BOTTOMIF INSTALLING THE WELLINGTON!!HEARTH PADSURFACEInformation specific to the installation of
58 RATING LABEL REPRESENTATION DXV35 DT3
59 THIS PAGE LEFT BLANK INTENTIONALLY
60 THIS PAGE LEFT BLANK INTENTIONALLY
61 MENDOTA WARRANTY QUALIFICATION & SERVICE REFERENCE FORM As a part of Mendota's on-going program of customer satisfaction, this Form ver
62 TAPE SHUT ------------------------------------------------------------------------------------------------------------------
63 MENDOTA EXTENDED PROTECTION AND LIMITED WARRANTY MENDOTA DXV35 DIRECT VENT FIREPLACE INSERT Mendota Division of Johnson Gas Appliance Company,
Johnson Gas Appliance Company 520 E Avenue N.W. - Cedar Rapids, IA 52405 Mendota Hearth Division
6 Specific Requirements for the Common Wealth of Massachusetts The information in this section applies to all installations performed in the Common
7 SAFETY AND WARNING INFORMATION READ and UNDERSTAND all instructions carefully before starting the appliance. FAILURE TO FOLLOW these instruc-tions
8 CONGRATULATIONS You are the owner of a world-class heat producing gas direct vent sealed combustion fireplace. This elegant, highly efficient Fire